• BAUMER BOURDON RPPY Industrial Intrinsic Safety
  • BAUMER BOURDON RPPY Industrial PS Intrinsic Safety

BAUMER BOURDON RPPY Industrial Pressure Switch Intrinsic Safety


Pressure switch for low and high pressure
Approval: ATEX EEx
Adjustable setpoint(s) and deadband
Measuring range: -50...0 mbar to 60...600 bar
Overpressure / Static pressure: max. 800 bar

BAUMER BOURDON RPPY Industrial Pressure Switch Intrinsic Safety

Main Features

  • Excellent repeatability
  • Fix dead band for control and alarm
  • Dead band adjustment for regulation
  • Intrinsic safety Hazardous area 0, 1, 2

Application

  • Power generation safety equipment
  • Pressurized chambers control
  • Liquid level control

Technical Data RPPY3 - RPPY7
Pressure range -200 mbar ... 0 to 60 ... 600 bar
Temperatures Pressure range codes 101 to 153 Medium: -15 ... +150 °C / Ambient: -25 ... + 70 °C (T5) / -25 ... + 55 °C (T6) / Storage: -40 ... + 70 °C
Pressure range codes 200 to 602 Medium: -50 ... +200 °C / Ambient: -25 ... + 55 °C (T6) / Storage: -40 ... + 70 °C
Electrical connection Terminal block with plastic cable gland for Ø 7 to 10.5 mm